    1.空调系统划分:洁净空调系统更主要的作用就是消除热湿干扰及尘埃污染,以便保持实验室内的空气品质。目前,洁净空调系统主要分为集中式、分散式、半集中式这3类。
    1. Air conditioning system division: the main function of clean air conditioning system is to eliminate heat and humidity interference and dust pollution, so as to maintain the air quality in the laboratory. At present, there are mainly centralized air conditioning systems.
    2.洁净室压差控制:由于实验室内的洁净室与其他房间要维持稳定的压差,所以在实验室洁净空调系统设要遵守2条规范标准。
    2. Clean room pressure difference control: since the clean room in the laboratory and other rooms should maintain a stable pressure difference, two standards should be followed in the design of clean air conditioning system in the laboratory.
    3.新风量计算:想要准确计算量计算必须有3个参数,第1个是补偿室内排风量和保持室内正压所需新风量之和,第2个是室内每人新风量不应小于40m?/h,第3个是新风量取保持正压所需新风量与补偿室内排风量之和。
    3. Calculation of fresh air volume: in order to accurately calculate the amount of air, there must be three parameters: the first is the sum of compensating the indoor exhaust air volume and maintaining the indoor positive pressure; the second is that the outdoor air volume per person in the room should not be less than 40m? / h; the third is the sum of the fresh air volume required to maintain the positive pressure and compensate the indoor exhaust air volume.
    实验室装修
    4.送风量计算:需要按照换气次数来计算,且洁净室的洁净度等级不同,换气次数也不同。具体来说,万级、10万级、100万级洁净室的换气次数分别为25h-1、15h-1、10h-1。此外,计算时可以选几个热湿负荷较大的房间,根据热湿负荷数值来计算房间送风量。
    4. Calculation of air supply volume: it needs to be calculated according to the air change frequency, and the air change times are also different when the cleanliness level of the clean room is different. Specifically, the air change times of 10000, 100000 and 1000000 clean rooms are 25h-1, 15h-1 and 10h-1 respectively. In addition, several rooms with large heat and humidity load can be selected to calculate the room air supply volume according to the heat and humidity load value.
    5.空调方案确定:所谓空调方案,主指气流组织选择,且有技术要求、送风与回风指标这2个参数。参数由实验室使用者提供,按生物制品生产洁净要求设计。
    5. Determination of air conditioning scheme: the so-called air conditioning scheme mainly refers to the selection of air distribution, and has two parameters: technical requirements, air supply and return index. The parameters were provided by laboratory users and designed according to the requirements of biological product production.
    6.空调机组设计选型:首先来看机组内部,其内部要光洁,且易于清洁,内部表面与内部零件材料要耐腐蚀。其次来看表冷器冷凝水排出口,此设备应具备自动防倒吸功能。此外,压差计用于机组内各级空气过滤器前后,并做好箱体密封。
    6. Air conditioning unit design and selection: first of all, the interior of the unit should be smooth and clean, and the internal surface and internal parts should be corrosion-resistant. Secondly, the condensate water outlet of the surface cooler should have the function of automatic anti back suction. In addition, the differential pressure gauge is used before and after air filters at all levels in the unit, and the box is sealed.
    7.制冷机房设计:这方面的设计必须根据前面这6项内容来确定,只有这样才能真正做好实验室洁净空调系统设计。
    7. Refrigeration room design: this aspect of the design must be determined according to the above six items, only in this way can we really do a good job in the laboratory clean air conditioning system design.