    1.二级及三级无菌室符合卫生行业标准:WS233-2002 《微生物和生物医学实验室生物安全通用准则》。
    1. The secondary and tertiary aseptic rooms meet the health industry standard: ws233-2002 general biosafety guidelines for Microbiology and biomedical laboratories.
    2. 二级(P2)无菌室为万级、局部百级,符合目前世界通用的美国联邦209E标准。
    2. Grade II (P2) aseptic room is grade 10000 and local Grade 100, which meets the current world-wide federal 209E standard.
    二级无菌室包含高、中、初效过滤系统,小型空调系统,层流送风,井式回风。更衣间及风淋室采用人体自动感应系统。
    The secondary sterile room includes high, medium and primary efficiency filtration system, small central air conditioning system, laminar air supply and well return air. The dressing room and air shower room adopt human body automatic sensing system.
    3.各系统技术指标如下:更衣间及操作间送风口风速≥0.3米/秒,风淋室风速≥15米/秒,操作间与环境静压差≥5Pa,系统噪声≤60dB.
    3. The technical indexes of each system are as follows: the wind speed at the air supply outlet in the dressing room and operation room is ≥ 0.3m/s, the wind speed in the air shower room is ≥ 15m / s, the static pressure difference between the operation room and the environment is ≥ 5pa, and the system noise is ≤ 60dB
    4.三级(p3)无菌实验室除具有二级无菌室的特点外,还专门设立了电子互锁门、传递窗门互锁、环氧树脂自流平地面、下水消毒设施。配置二级生物安全柜,实验室及缓冲间均为负压空间,实验间的相对压强为-30Pa—-40Pa,缓冲间的相对压强为-15Pa—-20Pa。
    无菌室装修
    4. In addition to the characteristics of level II aseptic room, level III (P3) aseptic laboratory has also specially set up electronic interlocking door, transfer window door interlocking, epoxy resin self leveling ground and sewage disinfection facilities. It is equipped with level II biosafety cabinet. The laboratory and buffer room are negative pressure space, the relative pressure between the laboratory is - 30Pa - 40Pa, and the relative pressure between the buffer room is - 15pa - 20Pa.
    无菌室装修技术要求:
    Technical requirements for decoration of sterile room:
    1.工作室应矮小、平整,高2.2—2.3米,内部装修应平整、光滑,无凹凸不平或棱角等,四壁及屋顶应用不透水之材质,便于擦洗及杀菌。
    1. The studio shall be small and flat, with a height of 2.2-2.3m. The internal decoration shall be flat and smooth without unevenness or edges and corners. The four walls and roof shall be made of impermeable materials to facilitate scrubbing and sterilization.
    2.室内采光面积大,从室外应能看到室内情况。
    2. The indoor lighting area is large, and the indoor situation can be seen from the outside.
    3.为保证无菌室的洁净,无菌室周围需设缓冲走廊,走廊旁再设缓冲间,其面积可小于无菌室。
    3. In order to ensure the cleanness of the sterile room, a buffer corridor shall be set around the sterile room, and a buffer room shall be set next to the corridor, which can be smaller than the sterile room.
    4.无菌室、缓冲走廊及缓冲间均设有日光灯及供消毒空气用紫外灯,杀菌紫外灯离工作台以1米为宜 ,其电源开关均应设在室外。
    4. The sterile room, buffer corridor and buffer room are equipped with fluorescent lamp and ultraviolet lamp for disinfection air. The sterilization ultraviolet lamp should be 1m away from the workbench, and its power switch should be set outdoors.
    5.无菌室与缓冲间进出口应设拉门,门与窗平齐,门缝要封紧,两门应错开,以免空气对流造成污染。
    5. Sliding doors shall be set at the inlet and outlet of the sterile room and buffer room, the doors shall be flush with the windows, the door seams shall be sealed tightly, and the two doors shall be staggered to avoid pollution caused by air convection.